Technical Specifications

  • Standard: IEC 60947-3

  • Rated current Ie (A): 32, 40, 63, 80, 100

  • Rated voltage Ui (V AC): 230/400

  • Rated insulation voltage Vi (V AC): 500

  • Number of poles: 1, 2, 3, 4

  • Degree of protection: IP20, with connected conductors

  • Electrical life (times): 1,500

  • Mechanical life (times): 8,500

  • Rated short-time withstand current 12 Ie: 1 s

  • Mounting position: Any

  • Conductor cross-sections

  • Solid and stranded (mm²): 0.75-35

  • Finely stranded with end sleeve (mm²): 0.75-25

  • Terminal tightening torque (N·m): 2.5

  • Ambient temperature (ºC): -25~+45, max. 95% humidity

  • Storage temperature (ºC): -40~+75

  • Altitude Max. (meters): 2,000

Features

  • The handle provides a clear indication of the contact position

  • Adequate printing of all data on the front provides long-term identification

  • Based the technology of MCB series 3SB1-63N, similar design to series 3SB1-63N.

  • Matched with series MCB 3SB5, 3SB52, 3SB1-63N

  • Full sets of accessories