Technical Specifications

 

  • Standard: IEC 60947-3

  • Rated current In (A): 25, 40, 63, 80, 100

  • Rated voltage Un (V AC): 1P: 230/400; 2-4P: 400

  • Rated insulation voltage (V AC): 500

  • Number of poles (P): 1, 2, 3, 4

  • Rated short-time withstand current 20 In: 1 s

  • Degree of protection: IP20, with connected conductors

  • Electrical endurance (Cycles): 4,000

  • Mechanical endurance (Cycles): 10,000

  • Fire resistance according to IEC 60695: 960 ºC

  • Mounting position: Any

  • Busbar Connection: Pin type

  • Conductor cross-sections

  • Solid and stranded (mm²): 1-35

  • Finely stranded with end sleeve (mm²): 1-25

  • Terminal tightening torque (N·m): 2.5

  • Ambient temperature (ºC): -5 ~ +45, max. 95% humidity

  • Altitude (meters): Max. 2,000

Features

  • Adequate printing of all data on the front provides long term identification

  • Matched with series 3SB6