Independent power supply with build-in power source,directly draws power from the incoming end to avoid the risk of protection function failure caused by external power supply failure.
● Overload protection
● Short circuit protection
● Isolation
● Controlling
● Used in residential building, non-residential building, industry, energy and infrastructure
Functions
● Types 2 surge arresters
● Handling energy from distant/ indirect lightning strikes or from switching operations
● Feature lower protection level (Up)
● Recommended at the incoming of installation for locations with no exposure to direct lightning impulses
Technical specifications
● Standard: IEC 61643-1
● Type / test class: 2 / II
● Number of poles: 1P, 1P+N, 2P, 3P, 3P+N, 4P
● Type of current: AC
● Frequency (Hz): 50/60
● Rated voltage Un (V): 230/400
● Max. Cont. operating voltage U (V): 140, 275, 320, 385, 420
● Max. discharge current Imax (8/20) per pole (kA): 10, 20, 40, 60
● Norminal discharge current In (8/20) per pole (kA): 5, 10, 15, 20
● Voltage protection level Up (kV): 1.0, 1.2, 1.2, 1.5
● Tov (Temporary overvoltage) withstand UT (5 s.) (V): 440
● Continuous operating current Ic (mA): < 1
● Degree of protection: IP20, with connected conductors
● Pluggable cartridge: Yes
● State indicator: Yes
● Integrated auxiliary contact: Yes
● Conductor cross-sections
● Solid and stranded (mm²): 2-35
● Finely stranded with end sleeve (mm²): 2-25
● Terminals
● Terminal tightening torque (N·m): 2.8
● Ambient temperature (°C): -5 ~ +40, max. 95 % humidity
● Storage temperature (°C): -40 ~ +75
● Connection Capacity (mm²): 1-25
Technical specification of the integrated remote signal contact
● Contact complement: 1 NO +1 NC
● Min. load: 24 V DC - 10 mA
● Max. load: 240 V AC - 1 A
Instruction of type code
Selection and ordering data
Selection and ordering data